About this tool
Single-phase or three-phase drop from current, length and the conductor resistance and reactance you supply.
ΔV = k·I·(L/1000)·(R·cosφ + X·sinφ); k = 2 single-phase, √3 three-phase; % = ΔV/V·100.
Formula: ΔV = k·I·L·(R·cosφ + X·sinφ)/1000
Example: Phase = Single-phase, Current (A) = 32, Cable length (m) = 50, Resistance R (Ω/km) = 0.727, Reactance X (Ω/km) = 0.08, Power factor cos φ = 0.9 → Voltage drop (%) = 0.959, Voltage drop (V) = 2.205.
R and X must come from the cable data you use; no cable table and no allowed drop is assumed.
Quick steps
- Enter your values — every field shows its unit.
- Press Calculate (or Try an example to see how it works).
- Read the results and copy them if you need them elsewhere.
The calculation runs in your browser. Nothing you type is sent to 1CLIK.
FAQ
How does the Voltage Drop Calculator work?
ΔV = k·I·(L/1000)·(R·cosφ + X·sinφ); k = 2 single-phase, √3 three-phase; % = ΔV/V·100.
What should I keep in mind?
R and X must come from the cable data you use; no cable table and no allowed drop is assumed.